HOME
Products and solutions for your requirements
Image
Rail products
Industrial products
The company
Contact us

UPS/C, an exceptional new item.
 
UPS/C Photo
e-mail
 
-
On-line double conversion system
-
Auto battery test
-
RS 232, RS 485, IBM AS400 interface
- SNMP
-
IGBT technology with high frequency switching
-
High crest factor
-
Feed capability for extreme load distortion so that output voltage distorsion is contained
-
Feed capability for unbalanced loads up to 100% unbalance
-
High efficiency from 25% of load
-
Easy installation and maintenance with complete frontal accessibility
-
Easy handling and use with guided start-up and sophisticated diagnostics
- Process sw and display in Windows environment
 
 

MODEL
Nominal output power rating (cos ø 0,8) -KVA 10 15 20 25 32
Nominal output power rating (cos ø 1) -KW 8 12 16 20 25,6
Nominal input voltage rating - Vca 380 ÷ 415 ± 10%
Nominal output voltage rating - Vca 220 ÷ 240
Output frequency - Hz 50 ÷ 60
Efficiency (CA - CA) % >=90 >=90 >=92 >=92 >=92
Ambient temp. UPS - °C 0 ÷ 40
Noise levels (per EN50091)
< 55 dB
Electro-magnetic compatibility
Compliant with EN 50091-2 (EC mark)
Serial communications interface
RS 232 - RS 485 (SNMP optional)
Hot standby configuration
2 UPS ( 1 UPS redundant)
Parallel configuration
To increase power up to 4 UPS or 3 + 1 redundant
Lead batteries (no. cells)
120 120 192 192 192
Battery test
Automatic - once a month
Battery temperature compensation
Optional
Inverter bridge
IGBT (high frequency switching)
Overload capacity
125% per 10'. 200% per 1'
Harmonic output distorsion
< 2%
Crest factor
3 : 1
Dimensions L x P x H - mm 620 x 660 x 1150 620 x 840 x 1300